Limitations of Use
With Arc protection, the environmental conditions and the risks at the working site shall be regarded. For example a test under the standard using a 4kA test current (Class 1) subjects the garment/fabric to an incident energy of 135 kJ/m2 ± 56 kJ/m2 (3.2 ± 1.2 cal/cm2) over a 500ms exposure at 18-28°C at 45-75% RH. If the working environment deviates from this temperature/humidity range the level of protection may be reduced. Exposure to higher incident energies or longer duration Arcs may result in the garment providing insufficient protection. Therefore risk assessments should be conducted prior to live working.
For full body protection, the protective clothing shall be worn in the closed state and other suitable protective equipment (e.g. helmet with protective face screen, protective gloves and footwear (boots) shall be used. No garments such as shirts, undergarments or underwear should be used which melt under Arc exposures – e.g. made of polyamide, polyester or acryl fibres. For maximum protection against Arc Flash Exposure garments should be worn as part of a layering system i.e. in conjunction with a shirt or other undergarment.